Annual maintenance schedule

Recurring maintenance for common building equipment, by frequency and month.

Scroll sideways for all 19 columns.

Equipment or systemTaskFrequencyJanFebMarAprMayJunJulAugSepOctNovDecPerformed byLast doneNext dueRecord kept
BoilerFlue gas temperature and composition; relief valves for leaks; low-water cutoff; pilot and burner clean; flame failure test; water and steam leaks; linkages; air leaks at damper sealsWeeklyXXXXXXXXXXXX
BoilerBlowdown adequacy; flue gas comparison; combustion air inlet; fuel system; belts and packing; gaskets; insulation and casing; steam control and pressure-reducing valves; water quality testMonthlyXXXXXXXXXXXX
BoilerClean water side and fire side; recondition or replace relief valve; recondition feedwater and fuel systems; clean electrical terminals; hydraulic and pneumatic valves; flue gas adjustment; eddy current test as requiredAnnuallyX
ChillerEvaporator and condenser coil fouling; compressor motor temperature; water quality; leak test; insulation; control operationWeeklyXXXXXXXXXXXX
ChillerVane control, motor load limit, load balance, chilled water reset settingsSemi-annuallyXX
ChillerLockout setpoint; clean condenser and evaporator tubes; eddy current tests; motor alignment and seals; oil analysis and filter; electrical connections; water flows; refrigerant levelAnnuallyX
Cooling towerFan motor; clean suction screen; water samples; make-up water switch; vibration; structure and fill; belts and pulleysWeeklyXXXXXXXXXXXX
Cooling towerLubrication; motor supports; motor alignment; drift eliminatorsMonthlyXXXXXXXXXXXX
Cooling towerClean tower of dust, scale and algae; bearings and drive belts; motor conditionAnnuallyX
Air handling unitFilters; casing leakage; damper actuators and linkageMonthlyXXXXXXXXXXXX
Air handling unitFilter rack integrity; coil finsAnnuallyX
FansBelts; pulleys; dampers; actuators; blade rotation and cleanliness; filters; moisture or growth in housingMonthlyXXXXXXXXXXXX
FansWiring connections; ductwork; coils; insulationAnnuallyX
PumpsLubrication; packing; motor-pump alignment; mountingsMonthlyXXXXXXXXXXXX
PumpsBearings and drive belts; motor conditionAnnuallyX
Electric motorsMotor conditionWeeklyXXXXXXXXXXXX
Electric motorsLubrication; packing; alignment; mountings; terminals; cleaningMonthlyXXXXXXXXXXXX
Electric motorsBearings and belts; condition; balanced power; over- or under-voltageAnnuallyX
Air compressorLeaks; run time; dryers; ventilation; oil level; drain condensate; operating temperatureDailyXXXXXXXXXXXX
Air compressorRelief valves; belts; intake filter pads; air-consuming devices; drain trapsWeeklyXXXXXXXXXXXX
Air compressorMotor bearing lubrication; system oilMonthlyXXXXXXXXXXXX
Air compressorCouplings; shaft seals; air line filters; mountingsAnnuallyX
LightingInspect for failed lamps or ballastsMonthlyXXXXXXXXXXXX
LightingInspect for dirt, degraded lenses, failed controlsSemi-annuallyXX
LightingClean lamps and fixturesAnnuallyX
Portable fire extinguishersVisual inspectionMonthlyXXXXXXXXXXXX
Portable fire extinguishersMaintenance check; date recordedAnnuallyX
Emergency lightingTest for 30 secondsMonthlyXXXXXXXXXXXX
Emergency lightingTest for 90 minutesAnnuallyX
Backflow preventersField testAnnuallyX
RoofInspect drains, downspouts, flashing, membrane and rooftop equipment; clear debris (spring and fall)Semi-annuallyXX

Recurring maintenance for common building equipment, by frequency, with a mark in each month the task falls due. The month marks are a starting spread; move each one to the month the building runs.

Sprinkler, fire alarm and emergency generator testing is not on this schedule. Follow the fire authority and the equipment maker for those.

Where a maker’s manual sets a different interval, it governs. Backflow test intervals are set by the state or the water supplier, and that rule governs.